Lift Station Alarms: A Telemetry Checklist for Small Systems
The design standard used across this region already says what a lift station must alarm on and where that alarm has to go. An upgrade starts by meeting that list reliably, then adds the few signals that warn you a problem is coming.
Key Insight
The design standard used in this region calls for lift station alarms on power failure, high water, pump failure and unauthorized entry, sent to someone who can act. Start an upgrade there, then add level trending and pump run data.
What the standard requires
Most lift station alarm questions are already answered in one document. It is the Recommended Standards for Wastewater Facilities, usually called Ten States Standards. Ohio EPA hosts a copy of the 2014 edition among its guidance documents. Pennsylvania systems should confirm with DEP which design standard applies to their project.
Section 46 is short. It says "alarm systems with a backup power source shall be provided for pumping stations." The alarm must activate on "power failure, dry well sump and wet well high water levels, pump failure, unauthorized entry, or any other cause of pump station malfunction."
It also says where the alarm has to go. The first choice is a municipal facility staffed 24 hours a day. If there is no such facility and the station lacks 24-hour holding capacity, the alarm goes to municipal offices during working hours and to the home of the person responsible for the station after hours. A local light and horn "may be acceptable in some cases," depending on location, holding capacity and how often someone inspects the station.
That is the floor. A modern remote telemetry system meets it and records what happened, which matters later in this checklist.
The required signals, one by one
Each required alarm has a sensor behind it, and each sensor has a typical way of failing. The table below is a starting point for walking a station with a vendor.
| Signal | What senses it | Common weak spot | What a good alarm looks like |
|---|---|---|---|
| Power failure | A power monitor or relay on the incoming service. | The alarm unit shares the station's power and goes dark with it. | The alarm runs on its own battery and reports the outage. |
| High water (wet well and dry well sump) | A level transmitter setpoint, a float switch, or both. | One sensor runs the pumps and raises the alarm, so one failure hides the other. | A separate high level float wired apart from the level controller. |
| Pump failure | Overload and fault contacts, plus a run signal from each pump. | Only the overload is wired, so a pump that is called but never starts goes unreported. | An alarm when a pump is called to run and no run signal comes back. |
| Unauthorized entry | A door or hatch switch. | The switch gets bypassed because routine visits keep setting it off. | A short delay and a way for crews to log their visit, so real entries stand out. |
Backup power for the alarm system is part of the requirement, not an extra. A power failure alarm that needs station power to send itself is the most common gap in older installations. The phrase "any other cause of pump station malfunction" also leaves room for whatever else a given station needs, such as a generator fault.
The signals worth adding
A few more signals are worth wiring in while the panel is open. None of these are in section 46. They are common practice because they are cheap to add during an upgrade and pay off the first time they catch something early.
- Continuous wet well level. A level trend shows inflow rising after rain, a pump that takes longer each cycle, or a slow climb that has not reached the alarm yet.
- Pump run time and starts. A pump that starts more often or runs longer than its partner is usually wearing, clogging or losing capacity.
- An independent high level float. If the level sensor fails, a separate float can still start a pump and raise the alarm.
- Communication loss. A station that stops reporting should raise its own alarm. Silence is not the same as healthy.
The required alarms tell you something has gone wrong. Level and run data tell you it is about to.
Getting the alarm to a person
An alarm that nobody acknowledges is the old red light on a pole with a longer wire. The callout design matters as much as the sensors. A good system calls the first person on the list, waits for an acknowledgment, and moves to the next person if none comes. Every step is logged with a time, so after an event there is no question about who knew what and when.
The list itself needs an owner. Phone numbers change when people retire or switch shifts, and a callout list nobody updates fails quietly.
The link back to the office is usually cellular or radio. Both work, and the choice depends on terrain, the number of sites and who will maintain the system. We compare them in cellular vs. radio telemetry for water utilities. One point belongs here too. Carriers retire old networks. The FCC's consumer guide listed AT&T finishing its 3G shutdown by February 2022 and Verizon by December 31, 2022, and it warned that connected devices beyond phones could be affected. Any cellular alarm unit should be on a current network with a clear replacement path.
For an example of cellular telemetry tying remote sites back to a plant, see the Canal Fulton water tower case study.
Overflow reporting is now electronic
When a lift station does overflow, the paperwork has changed. Under EPA's NPDES eReporting rule, permittees that must submit Sewer Overflow/Bypass Event Reports had to begin submitting them electronically by December 21, 2025, unless their regulatory authority directs otherwise or they received a waiver.
In Ohio, the appropriate district office is notified by phone, and a noncompliance report is then submitted electronically through the eBusiness Center. Either way, the report asks what happened and when. Time-stamped alarm and level records turn that from a reconstruction into a printout. Level data shows how long the wet well stayed high and when pumping caught up.
Keep the station off the open internet
Remote access is useful, and it is also the part attackers look for. On July 30, 2026, CISA warned that threat actors were targeting exposed PLCs at water and wastewater systems of all sizes, including through "cellular modems installed by operators, vendors, or system integrators that may not be documented." A lift station upgrade is a good time to document every modem and route remote access through a VPN or gateway rather than straight to the controller. Our post on secure remote access for water systems covers the federal guidance in more depth.
An upgrade checklist
These ten items make vendor quotes comparable. Each one is a line in the scope. Item nine is the one most often skipped. An alarm that is never tested is an assumption, and a logged test on a schedule is the only way to know the high water float still floats.
- The four required alarms: power failure, high water in the wet well and dry well sump, pump failure and unauthorized entry.
- Backup power for the alarm and telemetry equipment itself.
- An independent high level float, wired apart from the primary level sensor.
- A callout list with acknowledgment and escalation, and a log of every step.
- A data logging interval for level, pump status and run time, and where that history is stored.
- The communication path, and who owns the SIM card or radio license.
- The remote access method, with no controller directly reachable from the internet.
- As-built drawings that match the panel as installed.
- A written test procedure for every alarm, run at startup and on a schedule after.
- Training for every person on the callout list.
The panel that carries these signals is a design decision of its own. Our guide to pump station control panel specifications covers that side, and our custom control systems work builds the panels. For utilities running a mix of stations, tanks and plants, the municipal water and wastewater page shows how the pieces connect.
Frequently Asked Questions
What alarms are required at a sewage lift station?
Section 46 of the Recommended Standards for Wastewater Facilities (Ten States Standards, 2014 edition) calls for alarm systems that activate on power failure, dry well sump and wet well high water levels, pump failure, unauthorized entry, or any other cause of pump station malfunction. Ohio EPA hosts a copy of this standard among its guidance documents. Pennsylvania systems should confirm with DEP which design standard applies to their project.
Does a lift station alarm have to call someone?
Generally, yes. The standard says alarms shall be transmitted to a municipal facility staffed 24 hours a day. If no such facility exists and the station lacks 24-hour holding capacity, the alarm goes to municipal offices during working hours and to the home of the responsible person off hours. A local light and horn may be acceptable in some cases, depending on location, holding capacity and inspection frequency.
What should you monitor at a lift station beyond the required alarms?
The most useful additions are a continuous wet well level trend, pump run time and starts, an independent high level float that works even if the main level sensor fails, and a communication loss alarm so a silent station is never mistaken for a healthy one.
Does a lift station alarm system need backup power?
Yes. Section 46 of the Ten States Standards says alarm systems with a backup power source shall be provided for pumping stations. Power failure is one of the conditions the alarm must report, so the alarm has to keep running when the station loses power.
Cellular or radio for lift station telemetry?
Either can work. Radio suits utilities with line of sight between sites and staff to maintain the system. Cellular suits scattered sites and small staffs, as long as the carrier has coverage at the station and remote access is secured. Many utilities use both.
Do sewer overflows have to be reported electronically?
Under EPA's NPDES eReporting rule, permittees required to submit Sewer Overflow/Bypass Event Reports had to begin submitting them electronically by December 21, 2025, unless their regulatory authority directs otherwise or they received a waiver. In Ohio, noncompliance reports are submitted electronically through Ohio EPA's eBusiness Center.
Services:
Environmental Compliance
Continuous monitoring and automated reporting to keep plants compliant
Custom Control Systems
Purpose-built control systems for efficient operation
Ready to ensure compliance and optimize your systems?
Let's discuss how our monitoring solutions can keep your operations running smoothly and meet regulatory requirements.