What an Inspector Checks on a Parshall Flume

Most open channel flow errors are not electronic. They are in the concrete and in where the level sensor points, and an operator can find most of them with a level, a tape and a rule.

Control Associates
Control Associates

Key Insight

A Parshall flume only measures correctly when it is level, the approach is straight and clean, and the head is read two thirds of the way back along the converging section. EPA's inspection manual lists the checks, and most of them need no instruments.

Why the structure matters more than the electronics

A flume or weir is the primary device, and the sensor above it is only as good as the structure it reads. EPA's NPDES Compliance Inspection Manual describes the pair this way: the primary device is a standard hydraulic structure where the depth of water at a set point corresponds to a flow rate, and the secondary device measures that depth and converts it to flow. A perfectly calibrated sensor on a flume that has settled out of level still reports the wrong number.

The margin is smaller than it looks. The Bureau of Reclamation's Water Measurement Manual says Parshall flumes can reliably measure free flow within 3 to 5 percent, plus head detection error, if standard dimensions are attained during construction, the flume is correctly set, and it is operated and maintained as recommended. The inspection tolerance is 10 percent. A flume that is a little out of shape and a sensor that is a little off can use up that margin together.

The manual sorts the usual problems into four kinds. Faulty fabrication means rough surfaces, critical dimensions out of tolerance, or throat walls that are not vertical. Improper installation means a device set too close to a pipe elbow, a valve or another source of turbulence, or set out of level. Sizing errors mean the device's recommended range does not cover the actual flows. Poor maintenance means corrosion, deterioration, and debris or solids that build up over time. The first three are built in at installation. The last one changes month to month, which is why the walk-around is worth repeating.

The checks below follow the order of the Parshall flume procedures in chapter 6 of the EPA inspection manual. When a check turns up something the operator cannot fix, our flow calibration and compliance team can take it from there.

The walk-around: seven checks for a Parshall flume

Each of these takes a look, a level or a tape. None of them need the meter.

  1. Straight, symmetrical and level. The flume should sit in a straight section of channel, symmetrical and level both across the flow and along it. The throat walls should be plumb.
  2. Standard dimensions. Parshall dimensions are strictly prescribed as a function of throat width. The Bureau of Reclamation adds that different sizes are not geometrically proportional, so a smaller flume cannot be checked by scaling a larger one.
  3. A straight approach. The upstream channel should be straight, horizontal and uniform in cross section for at least ten times the throat width, and the mouth of the converging section should be as wide as the channel with rounded transitions.
  4. Smooth entrance flow. Water entering the flume should be free of turbulence or white water, with velocity uniform across the width.
  5. Clean approach and discharge. Both should be free of accumulated solids. The manual notes that buildup may indicate a flume that is oversized or set incorrectly in the channel.
  6. Head measured in the right place. The level sensor or staff gauge belongs two thirds of the length of the converging section back from the beginning of the throat. The staff gauge should read zero at zero head.
  7. Free discharge. The downstream channel should be low enough for water to leave freely. A standing wave in the discharge section is good evidence of free flow. Water marks on the walls can show submergence at high flow.

Most open channel flow errors are in the concrete and in where the sensor points.

The checks for a weir

Sharp-crested weirs have their own list, and the details are small. From the same chapter:

  • The weir is perpendicular to the flow, and the crest is level across the whole channel.
  • The approach is straight for at least 20 times the maximum expected head, with no solids, debris, or oil and grease near the weir.
  • The crest edge is no more than 1/8 inch thick, square to the upstream face, chamfered about 45 degrees on the downstream side, clean and smooth.
  • The weir-to-bulkhead connection shows no leaks or cracks that let water bypass the crest.
  • The crest corresponds to zero on the secondary device.
  • The head is measured upstream at least four times the maximum head.
  • There is an air gap behind the falling water, and the nappe springs free of the weir plate.
  • On a V-notch, the head stays between 0.2 and 2.0 feet. Below 0.2 feet the nappe may not spring clear of the crest.

The 10 percent test

Once the structure checks out, the inspector compares numbers. The manual describes an independent head measurement with a yardstick or carpenter's rule at the proper point, converted to flow with standard tables or formulas. That flow is compared with the plant's totalizer or recorder. The plant's measurement should be within 10 percent of the inspector's. Ideally the comparison is made at several flow rates.

The totalizer gets its own check. During steady flow, the inspector reads the totalizer just as a new digit appears and starts a stopwatch, then reads it again 10 to 30 minutes later. The difference over the elapsed time gives a flow rate, which is compared with the flow from the head measurement. The totalizer passes if the two are within 10 percent, with the measured flow as the divisor.

Nothing stops an operator from running the same comparison. The manual suggests periodic monthly checks of the flow measurement system, and a monthly line in the log showing the head reading, the calculated flow, the meter reading and the percent difference is the record an inspector hopes to find.

What submergence does and how to spot it

A Parshall flume is rated for free flow. When enough water backs up from downstream, the upstream head no longer tells the whole story, and a meter still using the free-flow table reads high. The manual calculates percent submergence as the downstream head divided by the upstream head, times 100.

How much submergence a flume tolerates depends on its size. The Bureau of Reclamation gives the points at which discharge starts to drop: 50 percent for 1, 2 and 3 inch flumes, 60 percent for 6 and 9 inch flumes, 70 percent for 1 to 8 foot flumes, and 80 percent for 8 to 50 foot flumes. Above those, a correction is needed, and it notes that correcting for submergence greater than 90 percent does not provide reliable accuracy.

The signs are visible. The standing wave in the discharge section is missing. Water marks on the walls of the discharge section sit higher than they should. Something downstream, such as an obstruction, a constriction or a channel turn, is holding water back.

When to call for calibration

Some findings are past what a walk-around can fix. These are good reasons to bring in a qualified calibration:

  • The flume or channel has settled, cracked or been rebuilt.
  • The level sensor or transmitter has been replaced.
  • The monthly comparison misses 10 percent twice.
  • A permit renewal or inspection is coming.

For how often calibration is expected and what the record should hold, see how often wastewater flow meters should be calibrated. For a plant where unreliable level sensing broke the flow record, see our flow monitoring case study. We work with municipal water and wastewater plants on both the instruments and the records. EPA's 1991 Parshall flume inspection video is still a useful way to see these steps done.

Steve Briggs, Director of Sales Engineering at Control Associates
Flume not agreeing with the meter?

Talk to Steve, our Director of Sales Engineering, about checking the flow measurement system and calibrating the meter that reads your flume.

Call(440) 708-1770
Emailsteveb@controlassociatesinc.com

Frequently Asked Questions

Where should the level sensor be on a Parshall flume?

Two thirds of the length of the converging section back from the beginning of the throat. EPA's NPDES Compliance Inspection Manual tells inspectors to confirm the head is measured at that point, because the water surface slopes through the converging section and a reading taken anywhere else gives the wrong flow.

How accurate is a Parshall flume?

The Bureau of Reclamation's Water Measurement Manual says Parshall flumes can reliably measure free flow to within 3 to 5 percent, plus head detection error, if standard dimensions are attained during construction and the flume is correctly set, operated and maintained.

What is flume submergence?

Submergence happens when water downstream backs up into the flume so that flow is no longer free. EPA's manual calculates percent submergence as the downstream head divided by the upstream head, times 100. Past a limit that depends on flume size, the standard free-flow table no longer gives the right flow and a correction is needed.

How does an NPDES inspector test a flume?

The inspector checks the structure, then measures the head independently with a rule at the proper point, converts it to flow with standard tables or formulas, and compares that with the plant's totalizer or recorder. The plant's measurement should be within 10 percent of the inspector's.

Can an operator check a flume without instruments?

Yes, for most of the structural checks: level, cleanliness, the approach channel, the staff gauge position and signs of submergence. Calibration of the secondary device, the sensor and meter that turn head into flow, still needs a qualified source at least once a year under EPA's inspection manual.