When the Screens Go Dark, Can Your Plant Run by Hand?

Federal alerts on the 2026 attacks against water system controllers describe utilities in sustained manual operation. Running a plant by hand is a design feature, and it has to be kept and practiced to be there when it is needed.

Control Associates
Control Associates

Key Insight

Federal agencies now list manual operation as a defense for water systems. Plants that added automation one project at a time may no longer be able to run by hand, because the switches, gauges and know-how went with it. It can be designed back in.

A line in a federal alert

On July 30, 2026, a federal alert about attacks on water system controllers closed its opening paragraph on a phrase worth reading twice. CISA wrote that the activity "has resulted in boil water notices and sustained manual operations."

Read from inside a plant, that phrase has a picture attached. Someone standing at a pump with a radio. Someone reading a gauge on a tank and writing the number down. Someone deciding, without a screen, when to start the next pump. Not for a few minutes, but for as long as it takes.

The FBI and EPA published their own announcement the same day. Utilities in at least seven states had reported incidents since July 27, 2026. The agencies wrote that the impact on each one depended in part on its "capability to switch to manual operations." They described the immediate effect as "a loss of view, and in some cases function, of connected equipment."

Loss of view is the phrase to sit with. The pumps may still be running. Nobody in the office can see them. The agencies also noted that impact depended on whether a controller was monitoring equipment or controlling it. A plant that loses its eyes needs people at the equipment to look. A plant that loses its hands needs people at the equipment to act. Who carried out the attacks, and how, is a matter for the agencies. The question here is the plant.

How plants lost the hand controls

No one set out to remove the hand controls. They went one project at a time, and each project made sense.

A hand-off-auto switch on a starter became a button on a screen. A pressure gauge on a discharge line became a transmitter feeding a trend. A chart recorder became a historian. A notebook of settings became a set of values inside a controller. Each change made the plant easier to watch and easier to run from one place. Each one also moved a piece of the process out of reach of a person standing next to the equipment.

The other loss was people. Operators who knew the manual settings, and what the plant did when it was run by feel, retired. We wrote about that in the operator retirement cliff. Here it matters for a narrower reason.

A manual procedure nobody has performed in years is a guess.

The result is a plant that runs well when everything works and has fewer ways to keep running when the controller cannot be reached. That is not carelessness. It is what happens when each upgrade is judged on its own, and nobody is asked to account for what the plant can still do without it.

What running by hand actually takes

Running a plant by hand takes four things, and none of them is complicated.

The first is a way to start and stop each pump, blower and chemical feeder at the equipment, with the controller out of the loop. The second is a reading that can be trusted without the network: a pressure gauge, a sight glass, a staff gauge in the wet well, a float. The third is written setpoints and sequences, on paper, where the operator will be standing when they are needed. The fourth is people who have done it recently.

The fourth is the one that slips. The FBI and EPA list "practice and maintain the ability to operate OT systems manually" among their recommendations, and they are specific about what practice means. Continuity plans, fail-safe mechanisms, software backups and standby systems "should all be routinely tested to ensure safe manual operations." Hardware that has never been used in anger is only half of the answer.

Practice also finds the small failures that paper hides. A hand switch that was never wired through. A gauge with a cracked face. A valve that takes two people to turn. A card in the panel door that still lists a setpoint from three upgrades ago. Each one is easy to fix on a quiet Tuesday and hard to fix during an incident.

The plans are already due

Much of the paperwork for this already exists. On EPA's schedule, community water systems serving 3,301 to 49,999 people owe an updated emergency response plan certification by December 31, 2026. That plan has to identify "equipment that can be utilized" when an event threatens the system's ability to deliver safe drinking water. Ohio EPA also had its drinking water contingency plans rule out for comment through October 2, 2026.

When a plan says the plant will switch to manual, the equipment behind that sentence is a hand switch, a gauge and a printed card. If those are missing, the sentence describes a plant that no longer exists.

Designing it back in

Manual capability can be specified like any other feature of a control system. The list is short:

  • A hand-off-auto switch at each motor starter, wired so hand mode does not depend on the controller.
  • An independent high-level float that can start a pump if the controller does not.
  • Local indication on the measurements that matter most, readable at the equipment.
  • A printed operating card in the panel door, with setpoints and sequences.
  • A clean backup of the controller program, held by the owner. CISA recommends "a known clean backup of the PLC image."
  • A manual operation drill on a regular schedule, with the people who would actually do it.

These sit alongside the network side of the agencies' advice, which our telemetry exposure checklist covers. One works to keep the controller out of reach. The other keeps the plant running if that fails. Some of the agencies' advice is physical as well: the FBI and EPA recommend keeping controller key switches in the run position, so logic cannot be changed from afar. The oldest kind of security is a switch someone has to turn by hand.

There is a tension worth naming. Ohio's staffing rule lets some plants reduce operator hours based on automation and continuous monitoring, and it sends them back to full minimum staffing on the "removal or failure of automation or continuous monitoring." Our post on the staffing reduction rule covers the details. On the day that clause applies, the ability to run by hand is what makes it manageable.

Built to run either way

Since 1968, Control Associates has put control systems and remote telemetry into plants, and has seen what happens on the days they stop. The work we prefer leaves a plant able to run either way.

Steve Briggs, Director of Sales Engineering at Control Associates
Want to know if your plant can run by hand?

Steve can walk the plant with your operators and list what manual operation would take.

Call(440) 708-1770
Emailsteveb@controlassociatesinc.com

Frequently Asked Questions

What does manual operation mean at a water plant?

It means running pumps, valves and chemical feed at the equipment itself, using local readings such as gauges, sight glasses and floats, without relying on the control system or the network. Setpoints and sequences come from written procedures, and operators make the decisions a controller would normally make.

Why are agencies recommending manual operation capability?

After attacks on water system PLCs in July 2026, the FBI and EPA listed "practice and maintain the ability to operate OT systems manually" among their recommendations. They said the impact on affected utilities depended in part on their capability to switch to manual operations, and CISA reported that the attacks resulted in sustained manual operations.

Can a modern automated plant still be run by hand?

Only if hand controls and local indication were kept, or are added back. A plant where every pump start, reading and setpoint lives in the controller has no manual path when the controller is unreachable. Hand-off-auto switches, local gauges, independent floats and printed procedures restore one.

How often should manual operation be practiced?

The FBI and EPA say continuity plans, fail-safe mechanisms, software backups and standby systems should all be routinely tested to ensure safe manual operations. They do not set a frequency. A regular schedule that includes the operators who would actually do the work is the practical answer.